BESS Operations & Maintenance: The Challenge of Maintaining Performance Over Time

The completion of the installation and successful commissioning of a Battery Energy Storage System (BESS) represent significant milestones. However, the real challenge lies in maintaining its performance over time.

Even when initial tests confirm the required capacity and proper equipment operation, the gradual aging of batteries can reduce usable energy and, consequently, affect the financial performance of the installation.

One of the most significant factors affecting battery aging is temperature which, in combination with charging and discharging conditions and the operating State of Charge (SoC) range, influences the rate of degradation. This aging is associated both with the passage of time and the conditions under which batteries are stored (Calendar Aging), as well as with repeated charging and discharging cycles (Cycle Aging). In practice, operating conditions are not necessarily uniform across all parts of a system, which can lead to different aging rates among individual cells.

A characteristic example is thermal non-uniformity. Even when temperatures remain within the permitted limits, recurring variations may occur between different locations within a battery module or rack. These variations do not necessarily indicate a malfunction, as they may be related to design characteristics and technical trade-offs between the efficiency, complexity and cost of the cooling system. Nevertheless, systematically monitoring them is an important part of Operations & Maintenance (O&M), since long-term temperature differences can contribute to uneven cell aging.

This aging is primarily reflected in two key changes: capacity loss and increased internal resistance. In the first case, the amount of energy the battery can store is reduced, while in the second, electrical losses and voltage deviations during charging and discharging increase. When cells within the same series exhibit different behaviours, some may reach their permitted voltage limits earlier, restricting further charging or discharging, even though the remaining cells still have available operating margin. In this way, cell imbalance can affect the usable energy of the system. However, a reduction in usable energy does not necessarily correspond to an equivalent irreversible loss of capacity, as it may also result from operational imbalances.

The behaviour of Lithium Iron Phosphate (LFP) batteries is of particular interest, as voltage deviations between cells often become more pronounced near the upper and lower limits of charge and discharge. This is related to the characteristic Open Circuit Voltage–SoC (OCV–SoC) curve, which remains relatively flat across most of the SoC range but becomes steeper near its extremes. As a result, even small differences in SoC can cause significant voltage deviations in these regions, without necessarily indicating that a cell is defective. At the same time, voltage measurements taken during operation are also affected by current, temperature and electrochemical polarization, making it essential to compare historical measurements under equivalent operating conditions.

At this point, it is important to distinguish between deviations caused by SoC imbalance and those associated with actual differences in capacity or internal resistance. In the first case, cell balancing can improve the utilization of available energy, whereas in the second, it cannot reverse the irreversible degradation of the battery. Therefore, the same measured deviation may have different underlying causes and require different corrective actions. Simply observing a deviation is not sufficient to determine the appropriate corrective measure; the underlying mechanism must first be investigated.

For this reason, O&M should not be limited to monitoring Battery Management System (BMS) alerts. Systematic analysis of historical data, such as temperature variations, current distribution across parallel-connected racks and the evolution of cell voltages, enables the identification of changes that may go unnoticed through conventional monitoring. In parallel, periodic capacity tests, when conducted under predefined and comparable conditions, contribute to assessing available capacity and tracking the evolution of State of Health (SoH). Comparing the results against initial baseline measurements and projected degradation curves makes it possible to assess whether actual battery aging is progressing within expected limits or requires further investigation.

When recurring deviations are identified, the next step is to investigate their underlying causes and assess whether intervention is necessary. Depending on the findings, actions may include checking the performance of the cooling system, evaluating cell balancing or adjusting operating conditions. In this way, systematic monitoring and technical diagnostics lead to targeted interventions, while also enabling the early identification of patterns that could affect the system’s future performance.

Effective BESS management therefore requires continuous technical supervision, systematic use of operational data and proper coordination of maintenance activities. For the asset owner, working with a specialized technical partner can contribute to the early identification of operational deviations and the assessment of SoH evolution and available energy against degradation projections and contractual performance guarantees. In this way, technical decisions are aligned with the system’s long-term reliability and the protection of the investment.

At ZEPHIROS, with 30 years of experience in the energy sector, we combine technical expertise with advanced monitoring and energy asset management tools. Through our Technical Asset Management services and 24/7 Operations Control Center, we support continuous operational monitoring, performance assessment and the early identification of deviations, contributing to the effective management of energy assets and the protection of investment returns.